Precision-control-systems 5620 Bedienungsanleitung Seite 11

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 14
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 10
Page 11 of 14
.
12BOutput Conditioning Selection
The 5620 Power has a jumper-selectable output conditioning feature, located on the lower
circuit board, that changes the output voltage response time (Fig. 3-3).
This feature protects the controller from excessive in-rush current when connected to resistive
loads that have low resistance when cold. The three different response time settings are:
Fast: For resistive loads where the cold-to-hot resistance is nearly constant. (.045 sec
response time)
Ramp: For rapidly responding resistive loads where the load resistance increases less
than twice from cold to hot. (1 second response time).
Lamp: For rapidly responding resistive loads, such as tungsten filament lamps, where the hot
resistance is more than twice the cold resistance. (5 second response time).
Figure 3-3 Jumper positions for Fast, Ramp, or Lamp response time settings.
Seitenansicht 10
1 2 ... 6 7 8 9 10 11 12 13 14

Kommentare zu diesen Handbüchern

Keine Kommentare